TRANSFORMER SEMINAR |
|
|
|
“BUCK-BOOST” |
|
|
|
APPLICATIONS |
|
|
|
|
BUCK-BOOST TRANSFORMERS START OUT AS ISOLATION
TRANSFORMERS WITH OUTPUTS FROM 12 TO 48 VOLTS, WHICH GET FIELD CONNECTED AS
“AUTO” TRANSFORMERS TO INCREASE OR DECREASE VOLTAGE WITHIN A RANGE OF 5 TO
20 PERCENT. (ie, 208 T0 230 V) |
|
THEY DO NOT PROVIDE ISOLATION FROM THE SUPPLY
BECAUSE THEY ARE “AUTO” CONNECTED. |
|
|
|
|
|
|
CURRENT WILL FOLLOW PATH OF LEAST RESISTANCE |
|
|
|
|
|
|
|
|
|
|
|
1. SYSTEM PHASE |
|
|
|
2. SYSTEM FREQUENCY |
|
|
|
3. LINE VOLTAGE |
|
|
|
4. LOAD VOLTAGE |
|
|
|
5. LOAD KVA, AMPS OR |
|
HORSEPOWER |
|
|
|
|
1. 1-PHASE |
|
|
|
2. 60 HZ |
|
|
|
3. LINE - 189 VOLTS |
|
|
|
4. LOAD - 208 VOLTS |
|
|
|
5. LOAD - 4 KVA |
|
|
|
|
|
|
|
|
REFER
TO 1-PHASE GROUP I SELECTION CHART
IN SECTION VII OF CATALOG ATD-01. |
|
|
|
|
|
|
|
|
|
|
1.
1 - PHASE |
|
|
|
2.
60 HZ |
|
|
|
3.
LINE - 208 VOLTS |
|
|
|
4.
LOAD - 240 VOLTS |
|
|
|
5.
LOAD - 60 AMPS |
|
|
|
|
REFER
TO 1-PHASE GROUP II SELECTION CHART IN SECTION VII OF CATALOG ATD-01. |
|
|
|
|
|
|
|
|
|
|
1.
1 - PHASE |
|
|
|
2.
60 HZ |
|
|
|
3.
LINE - 240 VOLTS |
|
|
|
4.
LOAD - 208 VOLTS |
|
|
|
5.
LOAD - 14 KVA |
|
|
|
|
|
|
REFER
TO 1-PHASE GROUP II SELECTION CHART IN SECTION VII OF CATALOG ATD-01. |
|
|
|
|
|
|
|
|
|
|
1.
3 - PHASE |
|
|
|
2.
60 HZ |
|
|
|
3.
LINE - 208 VOLTS |
|
|
|
4.
LOAD - 230 VOLTS |
|
|
|
5.
LOAD - 80 KVA |
|
|
|
|
|
|
REFER
TO 3-PHASE GROUP I SELECTION CHART IN SECTION VII OF CATALOG ATD-01. |
|
|
|
|
|
|
|
|
|
|
|
|
1.
AIR CONDITIONERS |
|
|
|
2.
AC MOTORS |
|
|
|
3.
PUMPS |
|
|
|
4.
TANNING BEDS |
|
|
|
5.
CONTROL CIRCUITS |
|
|
|
|
|
STANDARD ISOLATION TRANSFORMER |
|
Handle large increases or decreases in voltage |
|
Provide electrical isolation and shielding if
required |
|
BUCK-BOOST TRANSFORMERS |
|
Handle small increases or decreases in voltage
(+/- 5 to 20%) |
|
Do not provide electrical isolation (because
they are “auto” connected) |
|
|
|
|
VOLTAGE CURRENT TEMPERATURE |
|
|
|
- 5 % + 5 % +
11 % |
|
|
|
- 10 % + 11 %
+ 23 % |
|
|
|
- 15 % + 17 %
+ 38 % |
|
|
|
|
DETERIORATE INSULATION |
|
|
|
NUISANCE TRIPPING OF BREAKERS |
|
|
|
INSUFFICIENT MOTOR TORQUE |
|
|
|
WASTED ENERGY AND MONEY |
|
|
|
|
|
|
%
RATED VOLTS % RATED TORQUE |
|
|
|
100% 100% |
|
|
|
90% 81% |
|
|
|
80% 64% |
|
|
|
|
SERVICE VOLTAGE CHANGED AFTER EQUIPMENT
INSTALLED |
|
VOLTAGE DROP IN POWER LINE |
|
ERRORS IN ORDERING EQUIPMENT |
|
UTILITY CUTBACK IN SOURCE VOLTAGE |
|
|
|
|
STANDARD ISOLATION TRANSFORMER |
|
16”H X 14”W X 11”D 125 LBS |
|
1O
KVA RATING |
|
|
|
BUCK-BOOST TRANSFORMER |
|
10”H
X 6”W X 5”D 24 LBS |
|
1
KVA RATING |
|
|
|
|
UL LISTED/CSA CERTIFIED |
|
UL 3R ENCLOSURES |
|
ALLOWABLE UNDER NEC |
|
EPOXY ENCAPSULATED |
|
(EXCEPT 50, 100, 150 VA) |
|
BROAD RANGE OF VOLTAGES |
|
TEN YEAR WARRANTY |
|