ACME ELECTRIC CORP
POWER DISTRIBUTION PRODUCTS DIVISION
TRANSFORMER SEMINAR
“BUCK-BOOST”
APPLICATIONS
WHAT ARE BUCK-BOOST TRANSFORMERS?
BUCK-BOOST TRANSFORMERS START OUT AS ISOLATION TRANSFORMERS WITH OUTPUTS FROM 12 TO 48 VOLTS, WHICH GET FIELD CONNECTED AS “AUTO” TRANSFORMERS TO INCREASE OR DECREASE VOLTAGE WITHIN A RANGE OF 5 TO 20 PERCENT. (ie, 208 T0 230 V)
THEY DO NOT PROVIDE ISOLATION FROM THE SUPPLY BECAUSE THEY ARE “AUTO” CONNECTED.
Slide 3
BASIC PRINCIPLE
CURRENT WILL FOLLOW PATH OF LEAST RESISTANCE
PRIMARY AND SECONDARY
HAVE SAME CAPACITY
BOOSTING CONNECTION
COIL VOLTAGES ADD
AUTO CONNECTION INCREASES KVA CAPACITY
DATA NEEDED TO SELECT BUCK-BOOST TRANSFORMER
1. SYSTEM PHASE
2. SYSTEM FREQUENCY
3. LINE VOLTAGE
4. LOAD VOLTAGE
5. LOAD KVA, AMPS OR
    HORSEPOWER
SELECTION EXAMPLE #1
1. 1-PHASE
2. 60 HZ
3. LINE - 189 VOLTS
4. LOAD - 208 VOLTS
5. LOAD - 4 KVA
1-PHASE GROUP I CHART
   REFER TO  1-PHASE GROUP I SELECTION CHART IN SECTION VII OF CATALOG ATD-01.
CONNECTION DIAGRAM
SELECTION EXAMPLE # 2
1.  1 - PHASE
2.  60 HZ
3.  LINE  -  208 VOLTS
4.  LOAD  -  240 VOLTS
5.  LOAD  -  60 AMPS
1-PHASE GROUP II CHART
    REFER TO 1-PHASE GROUP II SELECTION CHART IN SECTION VII OF CATALOG ATD-01.
CONNECTION DIAGRAM
SELECTION EXAMPLE # 3
1.  1 - PHASE
2.  60 HZ
3.  LINE  -  240 VOLTS
4.  LOAD  -  208 VOLTS
5.  LOAD  -  14 KVA
1-PHASE GROUP II CHART
    REFER TO 1-PHASE GROUP II SELECTION CHART IN SECTION VII OF CATALOG ATD-01.
CONNECTION DIAGRAM
SELECTION EXAMPLE # 4
1.  3 - PHASE
2.  60 HZ
3.  LINE - 208 VOLTS
4.  LOAD - 230 VOLTS
5.  LOAD - 80 KVA
3-PHASE GROUP I CHART
    REFER TO 3-PHASE GROUP I SELECTION CHART IN SECTION VII OF CATALOG ATD-01.
Connection Diagram B-B
BUCK-BOOST SLIDE CHART
       DEMONSTRATE SLIDE CHART
TYPICAL APPLICATIONS FOR BUCK-BOOST TRANSFORMERS
1.  AIR CONDITIONERS
2.  AC MOTORS
3.  PUMPS
4.  TANNING BEDS
5.  CONTROL CIRCUITS
GENERAL APPLICATION COMPARISON
STANDARD ISOLATION TRANSFORMER
Handle large increases or decreases in voltage
Provide electrical isolation and shielding if required
BUCK-BOOST TRANSFORMERS
Handle small increases or decreases in voltage (+/- 5 to 20%)
Do not provide electrical isolation (because they are “auto” connected)
EFFECT OF LOW VOLTAGE ON MOTOR OPERATION
VOLTAGE CURRENT     TEMPERATURE
- 5 %      + 5 %      + 11 %
- 10 %      + 11 %      + 23 %
- 15 %      + 17 %      + 38 %
OTHER EFFECTS OF LOW VOLTAGE ON MOTORS
DETERIORATE INSULATION
NUISANCE TRIPPING OF BREAKERS
INSUFFICIENT MOTOR TORQUE
WASTED ENERGY AND MONEY
EFFECTS OF LOW VOLTAGE ON MOTOR TORQUE
    % RATED VOLTS         % RATED TORQUE
       100%        100%
      90%          81%
      80%          64%
CAUSES OF VOLTAGE MISMATCH
SERVICE VOLTAGE CHANGED AFTER EQUIPMENT INSTALLED
VOLTAGE DROP IN POWER LINE
ERRORS IN ORDERING EQUIPMENT
UTILITY CUTBACK IN SOURCE VOLTAGE
GENERAL SIZE COMPARISON
STANDARD ISOLATION TRANSFORMER
16”H X 14”W X 11”D           125 LBS
    1O KVA RATING
BUCK-BOOST TRANSFORMER
    10”H X 6”W X 5”D                24 LBS
     1 KVA RATING
ACME BUCK-BOOST
FEATURES
UL LISTED/CSA CERTIFIED
UL 3R ENCLOSURES
ALLOWABLE UNDER NEC
EPOXY ENCAPSULATED
(EXCEPT 50, 100, 150 VA)
BROAD RANGE OF VOLTAGES
TEN YEAR WARRANTY